To break it down analytically, I have looked at the pipe properties as follows:
S = 15.8 in3
E = 24,000,000 psi
self wt = 30lb.ft
weight of water = 22lb.ft
Allowable stress = 48000psi per DIPRA
I submit that we can consider that the 8'-0" span with a joint in the middle conservatively as 2...
Brillant. I designed a complex foundation to span over this and it never occurred to me to move the pipe.
This is a critical utility and shutdown of the pipe would cost more time and money than a redesign of the foundation. This is a less than optimal solution for everyone involved, but the...
Does anyone have any pointers on how to identify the maximum support distance from a joint/fitting for a span of ductile iron pipe? The pipe in question is 8" diameter and carries water. Looking through the Ductile Iron Pipe Research Association literature and webpage, the closest information I...