First off, it's obvious that this is not being installed to code. A 250Hp motor under normal conditions is rated at 302amps. I'm assuming 480Vac@60Hz. Sizing for protection is not done by nameplate values. You say the circuit feeding this drive is rated for 200HP(240Amp,at least 300kcmil Cu...