    VSD Question

    First off, it's obvious that this is not being installed to code. A 250Hp motor under normal conditions is rated at 302amps. I'm assuming 480Vac@60Hz. Sizing for protection is not done by nameplate values. You say the circuit feeding this drive is rated for 200HP(240Amp,at least 300kcmil Cu...
  3. Ctrlfreak

    moving logix key?

    First off, does the program run on your desktop. This will verify that the activation is indeed on your desktop. I'll assume you've verified this. Here are some possibles that would cause this: · The activation file does not exist. · The operating system is preventing the file from being opened...