  1. rex2704

    Interpreting transformer phase shift in SKM PTW software

    Thank you once again davidbeach. I had tried that earlier - running load flow studies. But the LF report only gave me current magnitudes and not the angles. I may have missed something. Anyway, I called SKM and they said I should use +30 degrees for Yd1 vector group connection.
  2. rex2704

    Interpreting transformer phase shift in SKM PTW software

    Thanks davidbeach for your response. I will elaborate more on my problem. I am trying to analyze a fault record available from an overcurrent relay connected to the primary side of this transformer. The fault currents on the primary side are as follows: Magnitudes: Ia=Ic and Ib=Ia+Ic Phase...
  3. rex2704

    Interpreting transformer phase shift in SKM PTW software

    I am a little confused with how to interpret the transformer phase shift angle value in SKM PTW software. I want to represent a two winding, 3-phase wye-delta transformer in PTW. The details are as follows: Primary: HV, Wye connected Secondary: LV, Delta connected Vector Group: Yd1 (HV voltage...
  4. rex2704

    Testing Split Phase Protection CT

    I work for a utility in Canada. We have a split phase protection provided on a large AC generator. This protection has a current transformer with Shell type core. Please see the attached diagram for details. I wanted to perform a saturation test on this Current Transformer (CT). I know the...
  5. rex2704

    Ferroresonance on 6.6kV, Y0Y0 connected Voltage Transformers

    Yes, this Schneider document is really good. In fact this is the document I was referring to in my first post.
  6. rex2704

    Ferroresonance on 6.6kV, Y0Y0 connected Voltage Transformers

    To add to my earlier note on the types of VT... The third type that I have mentioned is CSA group 3 VT (rated for line-to-line but one terminal must be connected to ground). The voltage factor of 1.9UN, 8Hrs on a group 3 VT is designated as group 3C and CSA approves its use on ungrounded...
  7. rex2704

    Ferroresonance on 6.6kV, Y0Y0 connected Voltage Transformers

    Bronzeado, I am in a process of procuring these VTs. I am looking at ABB, SADTEM and GE as my options. I will post the p.u. cost when I get it. By the way, I am considering VT with a voltage factor of 1.9UN, 8hrs. The VT is 7200/120V. So 1.9UN (UN=4157V) will be about 7898V which is roughly 1.2...
  8. rex2704

    Ferroresonance on 6.6kV, Y0Y0 connected Voltage Transformers

    Thanks Scottf. I agree with all your comments. I am looking at having only one primary fuse per VT. When I read the term 'bushing' I thought that you meant a VT with those porcelain or epoxy insulators on top (which you get on outdoor VTs). At 6.6kV, indoor VTs have a bolted terminal right on...
  9. rex2704

    Ferroresonance on 6.6kV, Y0Y0 connected Voltage Transformers

    Thank you all for your responses. I also felt that line-to-line rated VT should be sufficient, if at all there is a risk of ferroresonance. From your comments (scottf and slavag) it appears to me that this solution is even better than having a dual secondary winding VT. I believe that the point...
  10. rex2704

    Ferroresonance on 6.6kV, Y0Y0 connected Voltage Transformers

    I would appreciate opinions from a few other experts too. Thanks!
  11. rex2704

    Ferroresonance on 6.6kV, Y0Y0 connected Voltage Transformers

    I work for a utility in Canada. I will first give some background on our network in question… We have 9MVA, 66kV/6.6kV, YND1 transformer. The HV side has a transmission line with the circuit breaker about 100kM away. The breaker probably performs only 3-pole operation. The LV side of this...
  12. rex2704

    Effect of Capacitor Banks on ground fault current

    Thanks davidbeach for replying to me. Well, I did contact SKM directly. They told me that they include the capacitive reactance of the capacitor bank in positive, negative and zero sequence networks in series. In the software, when I had entered the kVAR rating of the capacitor, I had found...
  13. rex2704

    Effect of Capacitor Banks on ground fault current

    I am working on a substation design using SKM power tools software (version 6.0). While working with the software, I have noticed that delta connected capacitor banks used for power factor correction give rise to ground fault currents in an ungrounded delta connected system. I had used a...