  1. haisa

    Difference between Earthing Reactor and Earthing Transformer

    Hello All. We are installing a 150MVA 330/132/33kV Y/Y/D Transformer. Is using an Earthing Transformer and Earthing Reactor together appropriate on the Tertiary winding for protection?
  2. haisa

    Short Circuit Rating

    What I want to know is whether the fault level of a substation has any effect on the choice of transformer to be installed at that substation. In this case the fault level of this substation according to my calculation is about 35KA while the short circuit withstand current rating of the...
  3. haisa

    Short Circuit Rating

    The Short Circuit MVA level of a 132/33kv substation is 20.31pu on 100MVA base. 2 x 60MVA Transformers were installed in the substation and the two packed up within a very short time. What factors do we consider in choosing a transformer for this substation please.
  4. haisa

    MagneticBalance Test

    Yes it is removed.
  5. haisa

    MagneticBalance Test

    Hello everyone, We conducted a magnetic balance test on a 30MVA, 132/33KV transformer on all the taps at both primary and secondary. The results showed that the sum of the two voltages are different from the applied voltage by about 6V to 10V. Is this acceptable? What could be wrong please.
  6. haisa

    tan delta

    Hello Engrs We conducted a tan delta test on a 30MVA, 132/33KV transformer recently using OMICRON CPC 100. At different voltages we had values like -6%, 0.5 % and 23%. What can we deduce from these. Iread that for good insulation the value should be around 0.007% what does the minus sign imply.
  7. haisa

    Horizon Circuit Breaker

    Hello, I am please looking for a detailed wiring drawing of a Hawker Siddeley 36KV Horizon Circuit Breaker. I could not find on their website.
  8. haisa

    Power

    Hello, What are the possible faults on transmission lines apart from long trees grounding the line? We have a 330KV line that keeps tripping but continue in service once closed back. We have cleared all vegetations under the line and all terminal equipment have passed insulation resistance test...
  9. haisa

    siprotec 7ut612 differential relay

    We have wired a siprotec relay on a 60MVA, 132/33KV Transformer. All readings looks okay but the differential current is too high and the differential current on blue phase is twice the other phases. What could be the possible reasons please.
  10. haisa

    Distance relay

    The relay is micom p 422. Is it possible to change its direction by changing the star point of the CT or the phase rotation of VT?
  11. haisa

    Distance relay

    Hello My distance relay at a 132/33kV terminnal sub-station is tripping due to faults on 33KV feeders. My suspicion is that it is looking at the wrong side. How do I confirm and correct this please?
  12. haisa

    Tan Delta test

    Please guide me How to conduct TAn DELTA test for power transformer.Pls give me some documents related
  13. haisa

    Power Transformer Storage

    Is it Possible to apply a low voltage of say 415V and then short the Secondary, so that the little current flowing keeps it warm?
  14. haisa

    Transformer Rating

    What I am actually after is the KVA Rating. So How do I find the Rated output Current of the Transformer?
  15. haisa

    Transformer Rating

    Actually the Voltage rating of the transformer is 132/33KV and I know that the percent impedance is the ratio of the rated volage that will produce rated current at the output if short circuited. But the volage I have at site is 415V. If I apply 415V the short circuit current obtain is small...
  16. haisa

    Transformer Rating

    Given a Transformer without nameplate, how do I find the find the Rating of the transformer at site where there is 415V?
  17. haisa

    Bucholtz Trip

    Thanks to you all. Isquaredr we are sure of the oil level. However I obsered that, when meggering the HV side the insulation resistance will drop at a certain stage and then rise again.
  18. haisa

    Bucholtz Trip

    We also suspected the relay to be faulty and changed it, but the transformer is still tripping.
  19. haisa

    Bucholtz Trip

    Hello Everybody We have a 30MVA, 132/33KV transformer that is tripping on bucholtz. We carried out Insulation resistance, magnitisation and short circuit tests which all shows a satisfactory result. The magnitisation and short circuit tests were carried out using 415V and the Insulation...