  1. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    Yes, the test was performed without fans ducting. Actually as rightly pointed out by everyone fans without ducting were of no use. I switched off the fan after sometime, and it made nearly no impact on the temperatures. Test was performed for about 2 hrs, and yes temperatures were stabilized...
  2. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    Today we have successfully test run the generator without cooling fan and with above arrangements: Max Power: 1.46 MW Max winding temp: 70 deg celcius Max Driven end bearing temp: 56 deg celcius Max Non Driven end bearing temp: 45 deg celcius Max vibration on generator bearing = 5 mm/sec
  3. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    This is the arrangement prepared to cool the alternator in absence of cooling fan. The air pressure is 4~5kg/cm2 and air flow is 7~8 m/sec measured on driven end side of alternator. Please comment on this air pressure & air flow, will this be sufficient to cool the genset on load?? Ambient is...
  4. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    Thanks all of you for your valuable suggestions & comments.
  5. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    An old crack has been found in the fan, which has dust ingress. This shows fan was damaged due to starting jerk which old crack couldn't bear. Fortunately no one was hurt in this incident.
  6. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    This pic shows complete engine & alternator.
  7. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    This picture shows air hose pipe connected to air sparger system. Please give your suggestion on this, after that we will try this on load.
  8. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    This is the location of fan originally installed on alternator near coupling.
  9. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    This is the damaged fan which was connected on driven end of generator. Can anyone comment is it only cooling fan or flywheel as well??
  10. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    The attached picture shows air sparger installed at non driven end of generator. It has 3 nozzles from which air will be supplied. Please comment for any observation.http://files.engineering.com/getfile.aspx?folder=39d4315f-ef44-4010-b2bf-8c23a9e8f16f&file=WhatsApp_Image_2016-12-20_at_20.37.49.jpeg
  11. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    Air sparging arrangement attachedhttp://files.engineering.com/getfile.aspx?folder=6bbf0b34-e847-4dcf-9e9f-8362c3304ef1&file=SAM_0426.JPG
  12. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    I am talking about alternator mounted fan and not engine radiator fan. This alternator fan got damaged during synchronization with a 10,000 KVA steam turbine generator. We are still in process of finding out exact cause of this damage. This is an old 1977 UNELEC generator and OEM parts are not...
  13. FARHANRAZA

    Diesel Engine Driven Generator Operation without Cooling Fan

    Dear All Members, We have been operating a Diesel Engine Driven Generator of following specs: Generator: Make: UNELEC France. Rating:1900 KVA, 1520 KW, 174 Amps, 6.3KV Diesel Engine: Type / Model:240-V16-GS-PE-1977 MFG'R: SACM Recently during startup of Generator after oil change, its cooling...