Can anyone direct me to where I can find some PRC-023 example worked out so that I can verify that I am doing it correctly?
This is the only resource that I have been able to find anywhere and even though it is much better than the original PRC document, it is still rather vague...
I agree with David, and it depends on the voltage level. 69kV+ I would never auto reclose for a bus fault. Same for for a SOTF. 9 times out of 10 (at least what I have seen) a SOTF arrises when the field forgets to pull the ground chains off the lines after working on them and then close the...