  1. Ali-rashid

    Parallel motorS run by one VFD

    We have two 30kw motors connected in parallel to a 75kw vfd. The motors are mechanically coipled to the load. In these cases, my knowledge says that the VFD can only work in V/F mode and vector control should not be used. But surprisingly, The VFD has only a vector mode and is set on Closed...
  2. Ali-rashid

    Wattage of a Braking resistor

    Hi we have a 20 tonnes crane run by a 60kw electric motor and its VFD. The dynamic braking resistor connected is 3.5ohm but we need to know the wattage of it and its model qnd brand is not clear. Is there a way to measure or calculate the wattage of the braking resistor?
  3. Ali-rashid

    Shipment consideration of MV softstarter

    Hi all. We have bought an AuCom MV softstarter panel and are arranging the delivery. We are already late in our project and need to do it by air, which needs the panel to be placed on its side horizentally. Some speciallists believe that doing so would damage the softstarter capacitors or other...
  4. Ali-rashid

    earth leakage relay vs insulation monitoring device

    Thanks Che. Your comment along with some search got me the answer.
  5. Ali-rashid

    earth leakage relay vs insulation monitoring device

    Hi All Can we use an earth leakage relay instead of an insulation monitoring device? Do they provide the same protection? Thanks
  6. Ali-rashid

    400v and 690 current rating of contactors

    I was choosing contactors for DOL starting a 690v motor. I was reviewing the specs of Schneider LC1F400M7. It is written: 200kW on 400vAC. This means the rated current is about 400Amps on 400vAC. 280kW on 690vAC. This means the rated current is about 280Amps on 690vAC. Why the contactors is not...
  7. Ali-rashid

    Unbalance Protection via 50N, 50G and 50GS

    Thanks every one. Your comments helped a lot understanding the scheme. I have one last question. Can R1 or R2 detect any ground faults on primary Delta windings or lines (the distance between CTs to Delta winding) considering that the primary is ungrounded?
  8. Ali-rashid

    Unbalance Protection via 50N, 50G and 50GS

    The source is on the delta side. The problem is that my field experience was that the unbalance load cause the relays to see currents and operate depending on pickup value. I was wondering if existence of neutral wire and a grounded star would make a path for the unbalanced current to go out of...
  9. Ali-rashid

    Unbalance Protection via 50N, 50G and 50GS

    I know ANSI46 can detect unbalance conditions very well but I am trying to understand the unbalance protections for a distribution transformer via 50N, 50G and 50GS. Our network uses delta/grounded wye transformers, so the protection scheme would be as below based on IEEE 242 book ...
  10. Ali-rashid

    ZIV

    Thanks Iran In case of protection relays for distribution in Iran usually Vamp, Micom, Fanox are used. But for Oil and Gas sector normally GE, Siemens and ABB are utilized. how does ZIV rank against these?
  11. Ali-rashid

    ZIV

    I have just heard of a brand for protection relays and comms solutions with name ZIV. I have not yet worked with their devices and don't know how is their quality. Is anybody familiar with them? How is their quality and level?
  12. Ali-rashid

    PT open delta and Wye wirings

    Hello all. I have some issues with PT wirings. your help is appreciated in advance. 1- can Wye PT wiring (3 PTs) provide phase angle measurements? 2- the figure below shows the connection of a single PT to Schneider Vamp40 feeder protection relay. the manual says that with this configuration...
  13. Ali-rashid

    Single phase motor type detection

    We have a single phase motor. we also have a vfd which supports PSC( permanent splitted capacitor) and single phase Shaded pole motors. The pictures of the motor plate and the capacitor on it are attached. Is this motor categorized in any of the supported types, i.e. PSC or shaded pole? How can...
  14. Ali-rashid

    High Amp contactor selection

    Hello I am struggling in finding the proper contactor for my requirement. I have an application which needs a contactor that satisfies the below characteristics: 690 Volt 1200 kW 1200 Amp please refer me to brands and models available in this range. please provide the exact model as I searched a...
  15. Ali-rashid

    Core Balance Selection guide

    I have recently studied core balance CTs and the only criteria provided for selection was the diameter. How should I choose the proper core balance for my application? For example consider having a 3*70mm2 three phase cables. what is the proper core balance diameter for this application? I have...
  16. Ali-rashid

    minimum operating time delay in overcurrent instantanous relay (function 50)

    Thank you all for your comprehensive information. JG2828, I appreciate your effort for providing screenshots, it was really helpful.
  17. Ali-rashid

    minimum operating time delay in overcurrent instantanous relay (function 50)

    Thanks for your instructions what is the typical range of breaker operating time? could you please provide me with the SEL overcurrent relay manuals? i was not able to download it form their site as they have not responded to my manual request.
  18. Ali-rashid

    minimum operating time delay in overcurrent instantanous relay (function 50)

    Hi everyone, I'm working as the technical director in a power equipment-supplying company. We work with different distribution protection relays. Some of these relays are FANOX relays which provide 50:instantaneous over-current function. The minimum operating time of 50p function in these...