Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

Search results for query: *

  1. jghrist

    Substation/HV grounding - Please let me know if my understanding is correct

    crshears, You may avoid a little discomfort by wearing conductive footwear when touching control cabinets. If you are not standing on a ground mat and touching a grounded structure when a high voltage ground fault occurs, you may experience fibrillation and death if you aren't wearing...
  2. jghrist

    480V, 300KW, BESS System breaker ground fault trip

    With a grd Wye - grd Wye connection to the utility, the BESS system may be furnishing zero sequence current to utility system unbalanced load. There also may be unbalanced plant load causing neutral current. If the neutral is grounded both at the service entrance and at the BESS, there could...
  3. jghrist

    Clearance Difference between 12.47 kV and 13.8kV Overhead Line

    The only change needed to the drawing is to change the voltage in the title block.
  4. jghrist

    Clearance Difference between 12.47 kV and 13.8kV Overhead Line

    The US National Electrical Safety Code (NESC) does not distinguish between 750 V and 22 kV with respect to required clearances.
  5. jghrist

    Residential load calcs

    kW demand is the difference between consecutive 15 min kWh readings times 4. If you have an average power use for 15 minutes of 1 kW, then the kWh usage for that period is 1 kW time 0.25 hr, or 0.25 kWh.
  6. jghrist

    Residential load calcs

    Some utilities provide more detail. I can go in the Duke Energy website, or use their mobile app, and download kWh readings in 30 minute intervals for my home energy meter. With this, you can calculate 30 minute demand values.
  7. jghrist

    panelboard schedule in an MS ACCESS table question

    You could do it in either program, but it's much easier to get to look nice in Excel. You can then copy and paste into an AutoCAD drawing.
  8. jghrist

    Equipment to solve phase unbalance

    Changing two phases will cause any 3Ø motors to run backwards (or try to until something trips or breaks).
  9. jghrist

    Calculated neutral current not matching measured neutral current

    If you use another phase for the 0°, you will get a different answer, but only because the angles are rounded to zero decimals. Note that the sum of all of the phase angle differences has to equal exactly 360°, but 119 + 119 + 123 = 361.
  10. jghrist

    Calculated neutral current not matching measured neutral current

    I arbitrarily chose 0° for the R (A1) phase angle. The difference between R & Y phase angles is 119° per the meter (Phi 12), so Y phase angle is 0 - 119 = -119°. The difference between B & R phase angles is 119° (Phi 31), so B phase angle is 0 + 119 = 119°.
  11. jghrist

    Calculated neutral current not matching measured neutral current

    For Full Load Phase Mag Angle deg Angle Rad Real Im R 180.2 0 0 180.2 0 Y 208.1 -119 -2.08 -100.89 -182.01 B 191.4 119 2.08 -92.79 167.40 N 19.88 -13.48 -14.61 Note...
  12. jghrist

    Calculated neutral current not matching measured neutral current

    What do the angles phi_12, phi_23, phi_31 represent?
  13. jghrist

    Circuit Protective Conductor CPC calculation and Design

    It's whatever current that is flowing through the conductor.
  14. jghrist

    Calculated neutral current not matching measured neutral current

    Note that B peaks considerably after the crossing of R&Y. This would occur if the angles of R&Y were 0 and -120, and the angle of B was 100 deg. Try moving the cursor on the meter to determine the zero crossing times of the three currents.
  15. jghrist

    Calculating Attenuation of GPR Transfer on OHL Grounds/Buried Grounds

    In this case, you can't just treat it as a second remotely connected grid with a current split factor. The buried bare 250 kcmil conductors will dissipate current into the earth. If the distance between grids is large, then there will be a voltage drop and a reduction in GPR, but it won't be...
  16. jghrist

    Calculated neutral current not matching measured neutral current

    The OP's equation only works if the currents are 120 deg apart. If R is 0 deg, Y is -120, and B is 110 deg, the neutral current would be 17.15. See attached spreadsheet.https://files.engineering.com/getfile.aspx?folder=13002f2a-9fd4-4d86-970f-19188bf6cc8c&file=Unbalanced_Currents.xlsx
  17. jghrist

    Motor kW Reading

    So, if you have a VFD efficiency of 0.96 and a measured power into the VFD of 114.5 kW, the power out of the VFD into the motor is 114.5*0.96 = 109.9 kW. If the motor has a 0.95 efficiency, then the power into the shaft is 109.9*0.95 = 104.4 kW.
  18. jghrist

    Calculating Attenuation of GPR Transfer on OHL Grounds/Buried Grounds

    If the ground connection between the main and remote ground grids is by overhead lines or insulated cables, you could treat the remote ground as a terminal and use software such as SES FCDIST to determine how much current flows to the remote grid and the GPR at the remote terminal. If the...
  19. jghrist

    Explanation for Importance and/or application of the "3*Zero Seq Current" for LG and LLG F

    True except for the becoming obvious part. In a single phase to ground fault, there is no net current in the unfaulted phases. The I0 is offset by I1 and I2 in the unfaulted phases.
  20. jghrist

    Transformer Differential with Reclosers

    Most microprocessor based recloser controls will have an input available that you could program to trip the recloser from the differential relay. Some may require an optional module. Non-microprocessor controlled reclosers will not have that capability.
Back
Top