6.2.4
Where a water supply serves both domestic and fire sprinkler systems, 5 gpm (19 L/min) shall be added to the sprinkler systemdemand at the point where the systems are connected, to determine the size of common piping and the size of the total water supply requirements where no provision...
I do not speak California, even though I grew up there
903.3.5.1 Domestic Services
Where the domestic service provides the water supply for the automatic sprinkler system, the supply shall be in accordance with this section
903.3.5.2 Residential Combination Services
A single combination...
Not an expert
Here is a good article
https://blog.qrfs.com/414-fire-sprinkler-testing-procedures-replacement-in-nfpa-25/
As far as which standard to follow the one adopted by the city/ country you are working in , by what the contract says, by other
Would say this does not apply to you::
1. NFPA 30 Scope section 1.1.2 item 9 - it says it is NOT applicable to "liquids in fuel tanks of... stationary engines" ; and
Start with IFC chapter 57
than NFPA 30 chapter 22
How are you connected to this?
Any FPE that can help you
Hum unprotected
If you have to comply with IFC, it will be in there
I am thinking nfpa 30 applies,
Will have to look at both of those
Should have asked is this a general question or planned install?,, plus in the USA?
If planned do you know what fire code is adopted
Without seeing it or a cross section
I would say yes combustible concealed space, sprinklers required
Because space is not less than six inches
Add another inch of insulation or something.
See what others say
Have not heard the question asked before.
Normally has to be in service at all times, yes down for maintenance, but should be in service as soon as possible
Ifc
507.5.2 Inspection, Testing and Maintenance
Fire hydrant systems shall be subject to periodic tests as required by the fire code...
If it looks like a fire alarm system,,,, I call it a fire alarm system.
I guess the smokes are spaced per 72?
Still should be monitored.
How many sq ft???
Well at first I was going to say monitoring required
Than the answer by the book is no
2021 ibc
907.6.6 Monitoring
Fire alarm systems required by this chapter or by the International Building Code shall be monitored by an approved supervising station in accordance with NFPA 72.
Exception...
As others have stated , will give my spin
1. Get the exact sds for the item stored. You need the brand and item, the owner is supposed to supply that. Make sure it is up to date
2. Find out for that location if and what edition of building and fire code is afopted. Can play into the answer...