  1. Mondy

    Current transformer calculations

    Hi Dan Thanks for your reply It is appreciated. Yes you are correct the phase angle error is very small in most measuring CTs and should be only a few minutes. I need some help if possible with the equations used in calculating the ratio and phase angle errors in measuring CTs as all the...
  2. Mondy

    Current transformer calculations

    Is there anyone that can help me as I really could do with some assistance? Cheers Ray
  3. Mondy

    Current transformer calculations

    Is there anyone that can help me as I really could do with some assistance? Cheers Ray
  4. Mondy

    Current transformer calculations

    Can anyone help me with the accurate calculation of ratio and phase errors in measuring current transformers? I would like to get a spreadsheet or something similar together for the design of toroidal bushing transformers and so far have not come up with any equations or methods that agree with...
  5. Mondy

    Current transformer calculations

    Can anyone help me with the accurate calculation of ratio and phase errors in measuring current transformers? I would like to get a spreadsheet or something similar together for the design of toroidal bushing transformers and so far have not come up with any equations or methods that agree with...
  6. Mondy

    Transformer impedance test calculations

    Just wanted to say thanks to both SparksAlot and ScottyUK for your invaluable help with this information and for the time you both spent helping me out. It is much appreciated and I owe you both a drink!! Cheers Ray
  7. Mondy

    Transformer impedance test calculations

    Hi SparksAlot Thanks my friend. From this am I right in saying that as the temperature goes up the core restivity increases and so the eddy currents reduce? Also what does the 0.00065 refer to? Cheers Ray
  8. Mondy

    Transformer impedance test calculations

    Hi Sparks Alot I think I have got most of it down, just a couple of questions. 1. How did you get to CORE = 23.7688+ from the measured was 24.7W? 2. The stray loss is 2.2163 WATTS @ 22deg.C and reduces due to the rise in resistance with temperature to 2.2163/k =1.8076W at 80deg.C is this...
  9. Mondy

    Transformer impedance test calculations

    Thats a good point, Is there no send facility via the forum as they have our addresses? Cheers buddy Ray
  10. Mondy

    Transformer impedance test calculations

    Hi SparkAlot Thanks for that my friend your effort is very much appreciated. I will have a good go with this. Your spreadsheet will be much appreciated if you would be so kind! Cheers Ray
  11. Mondy

    Transformer impedance test calculations

    Hi SparksAlot Many thanks for your time it is very much appreciated. Can you show me the equations you used to get your results. As I see it you came to the following using: Rated current @ 230v and 960VA = 960/230= 4.173 A Ratio up test voltage at rated current = (4.173A/2.188A)*...
  12. Mondy

    Transformer impedance test calculations

    Thanks SparksAlot If you could help me on this I would be eternally gratefull! OK here goes... all are measured values Hv (pri) resistance @ 22deg.C = 0.4978R Lv (sec) resistance as above = 0.0116R Voltage ratio Pri: 230v Sec: 25.5V = ratio 9.109 (24v rated on load at 40A or 960VA No-Load...
  13. Mondy

    Transformer impedance test calculations

    Hi Scotty Yes I agree with what your saying and this is almost definately the case the location is rural and +10% over volts is a regular occurrence for them apparantly, the iron saturation and hence the peaky input current is causing the issue, but there are other factors and that is why I...
  14. Mondy

    Transformer impedance test calculations

    Hi Dave & Scotty Thanks for your replies. No this is not a college assignment (although it feels a bit like one!) It is part of the analysis of a Norwegian transformer that is not performing at all well in the UK (at 240v + 10%) and is part of a large underfloor heating plan. These are the test...
  15. Mondy

    Transformer impedance test calculations

    Hi All Can anyone help me with the calculations involved in a transformer short circuit impedance test. I have the following data: Transformer rated voltage =230v Transformer rated power = 960VA Secondary short circuited during test ambient temperature during test = 22 deg.C Measured...
  16. Mondy

    Electrical Steel curves and magnetizing current

    Hi everyone Many thanks for all your replies. I was not originally concerned with inrush current (I am however very keen on learning a little more about this...) My main concern was just calculating with reasonable accuracy the no load rms current of transformers/coils wound on a particular...
  17. Mondy

    Electrical Steel curves and magnetizing current

    Thanks Edison I am not looking at this from the viewpoint of evaluating a transformer. I need to know the magnetizing current and watts loss of coils wound on a core of the steel material. I have the curves for the material but I cannot see how the magnetizing current at high flux densitites...
  18. Mondy

    Electrical Steel curves and magnetizing current

    Dear Experts Can anyone tell me how I can calculate the rms magnetizing current of a transformer when the only information I have for the core steel are curves for Watts Loss per Kg and Peak Magentic Field strength(A/meter) for any given value of flux density. As far as I can see, using the...
  19. Mondy

    Transformer Power Factor

    Thanks Stevenal OK I understand how you came to 3.69% regulation and R=(54.09/1440)% and Z is the quadrature sum of R+X, but how did you come up with X and 53.2VArs? Will this then evaluate to COS(ATAN(53.2/(1440+54.09+6.5)))= 0.99937 = 1 ? Cheers Ray
  20. Mondy

    Transformer Power Factor

    Hi All Sorry for the delay in replying. Yes the transformer is custom designed and so does not conform to any standards regarding loading. Here are the actual transformer details CORE : 160 x 85 x 60 mm. M5 (0.30 mm.) Fe.Weight : 6.29 kg. Bmax : 1.55 T. Cu.Weight ...