Hmmm I don't think so. An evidence storage room could end up storing all sorts of items, including chemicals, weapons, organic items, etc. Not to mention the client specifically requested extra exhaust capacity due to the smell of marijuana. Thank you for the comment though.
Good point on the humidity control as that will be important as well. Also will be keeping the space negative and exhausting outside. The values are honestly pretty similar, so I have no apprehension in using either. Thank you for the help!
Hey,
Currently working on a police project with an evidence storage room. I am looking for some kind of guidance on recommended exhaust rates for this type of space. 62.1 does not specifically address this kind of room, although I had though about using the same rate for a chemical storage...
Greetings,
Long time reader first time poster. A quick note on my background. I am new to the HVAC field (7 months) after working at a steel mill for a year after graduating from school with a B.S.M.E. I am on my second "start-to-finish" project after helping out here and there and learning...