From the answers provided, it seems that it is acceptable to lose control of a MV disconnector over an electrical fault in the heater or the light of a control box.
This does not make a lot of sense to me!
Any tips or suggestions from the more experienced? [bigears]
@crshears Actually I think there is no big difference in terms of continuity of service, since the 230 V AC are provided from the output of a UPS system installed in the nearest station ...
Dear all,
I'm checking a quote for a 25 kV Disconnector Switch and I noticed that in the attached circuit diagram the manufacturer uses 230 V AC (Europe) for all circuits, namely for the Control box auxiliaries (heating, light bulb, socket), the control circuit, the motor circuit and the...
Hello,
Could you please provide a link to the IEEE CT saturation tool?
Usually, the protection relay manufacturer provides some application examples which give some standard values for the X/R ratio.
BR,
cranky 108 thank you for your answer!
Unfortunately it is not easy for me to communicate with your above references as I live and work in Europe!
The system I am talking about does not have a catenary feeding line nor a copper neutral (you can click on the link to see a layout of the system)...
Dear Sirs,
I am trying to build a model of a DC Traction Power System, composed of 10 Traction Substations (TSS) feeding a third rail, also known as conductor rail, system (750 V DC).
The main objective is to build a representative model that will confirm the points where the max/min di/dt...
@Kiribanda
Please notice that:
[highlight yellow]We are experiencing several nuisance trips of the auxiliaries T/F CB when the main transformer is energized.[/highlight]
If I disconnect the residual CT connection there will be no tripping because this CT is the input for the 50N/51N...
@davidbeach
The installation was performed as described in your post:
Point one was connected through an insulator to the earthing bar of the cable compartment (no electrical connection), passed through the core balance CT and then terminated at the earthing bar of the cable compartment...
Thank you for your answers,
@RRaghunath
Relay auxiliary voltage comes from a different power supply!
@davidbeach
I have 4 similar substations, the problem occurs consistently at 2 of them since day one. (This may relate to the relation between inrush current and external grid impedance?)
For...
Dear Sirs,
We have a MV switchboard consisting of three CB's:
1) one connected to the 20 kV grid,
2) the second feeding a 3.3 MVA 3-winding transformer and
3) the third feeding the substation auxiliaries 50 kVA 2-winding transformer.
We are experiencing several nuisance trips of the...
Thanks for the answer prc!
"Approx 0.8 % volume increase for every 10 C temperature rise."
Do you mind sharing a source for this information? Does the same apply for a 10 C temperature decrease? According to your experience, 0.8 % volume increase for mineral or synthetic oil?
For this...
Hello everybody,
I had to work on an incident in a Traction Substation where a Hermetically sealed Oil Immersed Transformer, aka corrugated tank completely filled without conservator, tripped due to low oil level after shut down (in reality it did not trip, it just could not be brought back in...
@ Kiribanda
Thank you for your answer.
Nevertheless, I will have to disagree with you.
[highlight #FCE94F]The metallic screen is making an equipotential surface for the cable so that the insulation is
not subjected to unbalanced electromagnetic stresses[/highlight] and contain the electric...
First of all, thank you both for your answers!
@ Kiribanda
Nevertheless the problem remains, ie the separate ground return cable cannot contain the electric field within the cable core and the cable sheath shall not be safe to touch with the cable energized.
Please recall that I am talking...
@ 7anoter4
When voltage values like "2001-5000 V" or "2.4 kV" are mentioned in the NEC, should I consider them as phase-phase or phase to earth voltage values?
I did a quick search and found that, according to NEC,
[highlight #FCE94F]"110.4 Voltages.
Throughout this Code, the voltage...
Hello 7anoter4,
Thank you for the reply!
Regarding type MC cables, in the IEC world, these would probably be considered screened/shielded cables according to par. 9.1 of IEC 60502-1:
I have in mind that there are differences between USA & IEC specifications and that is why my main question...
Dear all,
In the IEC world, every cable designed for a voltage level greater than 1 kV shall have a metallic layer surrounding the core(s), par. 7.3 of IEC 60502-1.
With regard to safety of personnel, the above requirement ensures that the outer sheath of the cable will be safe to touch...
@waross
The first possibility may be the answer i was looking for since in europe we are not used to awg/kcmil units for conductor csa ...
The tools are not of high quality but they must have performed well in the past since we didn't have any complaints!
Regards,
George
Dear all,
In an attempt to install some THHN cables we damaged two of our cable stripping tools.
These tools were previously succesfully used for similar works on building cables with thermoplastic PVC insulation rated for 70 deg Celsius.
Αs the root cause of the tools damage, apart from bad...