The meter is not piped back to suction line, it is located before the test header, so the meter flows/discharge to drain.
So a metered test loop piped back to the suction line is not required as long a flow meter will be installed to achieved full flow test?
Hi All!
Is there any requirement to provide additional test loop around the fire pump if the system is already equipped with metered test header?
Thanks All!
The building was designed in accordance UFC (military), so both IBC 2012 and NFPA 101 were used.
Fire rating requirements of load bearing assemblies shall comply to IBC 2012. For non load bearing assemblies shall comply to NFPA 101 2015.
Thanks cdafd,
Currently the design provided a 2 hr rated gyp board ceiling to protect the insulation. The insulation itself is 15 mins rated as required by NFPA 101 for foam insulation. But since the room is required to have 2 hour separation, they said (designer) the ceiling should be 2 hr...
Sir's
I'm working on a 1-storey warehouse project with multiple fire areas. One of the area/room needs to be separated with 2-hr fire rated construction with the rest of the building. CMU walls were being provided as the 2-hr fire rated separation and they are constructed from floor up to the...