  1. Ennajjar

    underground connections need cable guard (conduteur earth)?

    Hello in underground connections you need a cable guard (conduteur earth) or not? Why
  2. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    I need to have 30 MW for each duct and `i` must be equales to 584 to have p = 30MW ! how can I increase the power to 30 MW for each duct with reasonable divergence that not exceed 50 cm between ducts?
  3. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    same methode for calculus I ? I=Sqrt{ΔӨ-WD*(0,5*T1+T2+n(T3+T4)/(R(T1+(1+λ1)*T2+n(1+λ1+λ2)*(T3+T4))}
  4. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    The three phases happen in the same duct (1 duct contains 3 cables== 1 circuit). Circuits are buried together in the power station then they are separated to be diffused in their designated post. The north post is connected to 3 circuits. So if one circuit contains 495 Then the three same...
  5. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    here is my power circuit the specifications mention that 30MW should be carryed to the North post(poste nord) but 303A isn't enough
  6. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    cable of 30 kV 630 mm2 aluminium conductor XLPE for ROC=ROE T'''4=1 / 2 / pi() * ROE * Ln((UE + Sqrt(UE ^ 2 - 1)) * fk) / 100 ROE= 1,5 C.M/W UE = 2 * LS(i) / DDEXT LS(i)= 1800 mm DDEXT= 200 mm ==> UE =18 FK=3147,04138 (with 450 mm between ducts ) T"'4=0,02662067104 T'4=0,24118306...
  7. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    In my situation I don't have concrete. Ducts are similar and puted in earth directly. Can I use this procedure even if I don't have concrete? If not what can I do? Thank You.
  8. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    the system must be balanced so I use the IEC 60287 2-1 ? I'm blocked on calculates External thermal resistance T4''' (about the method Neher-McGrath is for cables embedded in the concrete?,or I can use for my situation?)
  9. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    for calculate the current condition for laying cables: Synthetic insulated single core cables for rated voltages Uo / U = 18/30 kV (Um = 36 kV)
  10. Ennajjar

    CROSS-BONDING

    CROSS-BONDING in middle voltage distribution grids I need courses and information on subject I will be very thankful If you can guide me and help me. Thanks in advance. Ennajjar Mehdi
  11. Ennajjar

    help for electricity distribution (HTA) through underground cables (6 circuits)

    I'm studying Electrical engineering at faculty.I will be pleased If you can guide me and give me advices and directions to take for resolving some problems I meet during my internship. Actually, I'm working on a project about a medium voltage electricity distribution (HTA) through underground...