Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

Search results for query: *

  1. NickParker

    Choice of Excitation - LV vs MV Generators

    What determines the choice of excitation in low-voltage versus medium-voltage generators—specifically, PMG or AREP/auxiliary winding? I've observed that AREP/auxiliary winding excitation is commonly used in low-voltage diesel engine generators, while PMG is typically preferred for...
  2. NickParker

    Diesel Generator in parallel with steam generator

    Are you referring to having a separate control panel for each generator, along with a master control panel for load sharing?
  3. NickParker

    Diesel Generator in parallel with steam generator

    Can you elaborate it. Why is is a must?
  4. NickParker

    IEC LV MCCs - Withdrawable starter units

    Hello Mr. Che Kuan Yau, Thank you for your response! After discussing with my client, I confirmed that the clause "no (test supply) disconnections are required when the unit is in the test position" applies to certain vendors who are unable to provide a separate control power (via the sliding...
  5. NickParker

    Continuous monitoring of stator insulation when the machine is offline

    Does any one have experience with the Bender module for medium voltage?
  6. NickParker

    Continuous monitoring of stator insulation when the machine is offline

    Online monitoring refers to tests conducted while the motor or generator is in operation. Offline monitoring is performed when the machine is not operating. I came across a spec "Continuous monitoring of stator field winding insulation during the generator is offline shall be provided". You...
  7. NickParker

    IEC LV MCCs - Withdrawable starter units

    All outgoing units shall be executed as fully withdrawable units complete with test facilities, i.e. all connections to vertical busbars and outgoing power and control cables shall be via plug/sockets/sliding contacts and no (test supply) disconnections are required when the unit is to be put...
  8. NickParker

    Temperature rise of a coolant - Generators / Motors

    Is the high temperature rise in the water cooling circuit specified to lower pressure in the tubes to prevent leakage or to conserve water usage?
  9. NickParker

    Temperature rise of a coolant - Generators / Motors

    a) If the system operates as a single-pass (non-recirculating) setup, the temperature rise can be "unrestricted", constrained only by the flow rate, pressure, and the heat exchanger's material limits. Is my understanding correct? b) From API 541 - How does specifying the minimum temperature rise...
  10. NickParker

    Cables for temporary submersion

    We need to install light fixtures in an area expected to be submerged for approximately two weeks each year. We have chosen fixtures rated for both IP66 and IP68. Would standard XLPE, armored cables be sufficient for this application, or should we consider specialized cables for these conditions?
  11. NickParker

    ACB trips when the control power transfer from UPS A to UPS B

    Another question is whether there will be any issues with the stop push button (local or remote). For instance, if I have implemented a time delay in the circuit during the transition period, when the operator presses the stop push button (either local or remote), do they need to push it down...
  12. NickParker

    ACB trips when the control power transfer from UPS A to UPS B

    I’m considering using this type of capacitor trip device or an off-delay timer to maintain the transition period. However, since this is a motor circuit, it may also delay the trip on actual fault. The ACB has a Micrologic electronic trip unit; my question is whether the Micrologic unit...
  13. NickParker

    Temperature rise of a coolant - Generators / Motors

    . I came across an old discussion thread here, where it mentions that the maximum allowable outlet temperature (API 541) is 49°C. Does this imply that the cold primary coolant (air) temperature is approximately 56°C, which seems significantly higher than the typical ambient temperature of...
  14. NickParker

    Diesel Generator in parallel with steam generator

    Steam is generated from the boiler using the dual fuel (mgo & burning Voc (volatile organic compounds) when the cargo is loaded into the tanker. Depending on the heat value of the VOC gases generated from the cargo loading operation, excess steam shall be used to drive a steam turbine...
  15. NickParker

    Temperature rise of a coolant - Generators / Motors

    I understand the concept of temperature rise in windings, but I’m unsure about the temperature rise in a generator’s cooling system. There are two key temperatures involved: the cooling fluid’s inlet and outlet temperatures. The difference between them is the temperature rise of the coolant. My...
  16. NickParker

    ACB trips when the control power transfer from UPS A to UPS B

    Yes, that's how it should be, but here undervoltage release is solely used for Emergency shut down purposes (fail safe), not for monitoring the undervoltage . however since being a motor feeder, the breaker to be tripped on the 690V undervoltage or deadbus. Therefore, this feeder should have...
  17. NickParker

    ACB trips when the control power transfer from UPS A to UPS B

    Hi Mr. Che Kuan Yau, Thank you for your reply, 1. The control power is of 230V AC fed by 230V AC UPS distribution boards 2. The ESD relay, K2 (SIL 3 rated) is of 24VDC - always energized - when deenergized - the contacts of K2 de-energises the undervoltage release (MN); which inturn trips the...
  18. NickParker

    Diesel Generator in parallel with steam generator

    We have three diesel generators (3.5 MW) that need to operate in parallel with a 1.5 MW steam turbine generator (STG) on a tanker. Since the STG manufacturer already has the unit ready off the shelf, and management has decided to use it (long lead item). I understand that since the STG has...
  19. NickParker

    ACB trips when the control power transfer from UPS A to UPS B

    Actually the control circuit power to the MCC is fed from the UPS distribution board A and UPS distribution board B with automatic transfer happening in the MCC. (see the drawing below),
  20. NickParker

    ACB trips when the control power transfer from UPS A to UPS B

    I attempted to set a time delay for the undervoltage release (with a delay longer than the transition time between UPS A and UPS B), but the auxiliary relay KA1 still caused the breaker to shunt trip. One possible solution is to eliminate the shunt trip and rely solely on the undervoltage...
Back
Top