  1. STONE85

    Mv and Lv switchgear in the same switchroom

    Hello, We are in the uk and there is a proposal for a new switchroom to contain both 11kv and 415v switchgear. Are there any standards that say these should be in separate rooms or separated with a barrier of some kind as I understand that you do not want non mv qualified staff being able to...
  2. STONE85

    Pin out diagram of a TCon board.

    Hi, I know this is a bit general but does anyone have a pin out diagram for a 55332-cod TCON board for a Toshiba TV. Thanks
  3. STONE85

    Cable sizing to bs7671

    Hello, In regards to cable calculations to bs7671. If we have a cable that needs to run through a duct bank for a small section of its run say 5m and the remainder >80m is in a subway. When we derate can we ignore the duct bank portion? Thank you
  4. STONE85

    Trimble (Amtech) question

    Hello, I have a question about diversity and load utilisation factor with Trimble software. Say we have a 3ph 400v 150kW load with 0.8 pf which gives 187.5 kVA and we also have a diversity of 0.8 and a load utilisation factor of 0.9. Applying these factors we will end up with a kVA of 135kVA...
  5. STONE85

    Transformer Protection schemes

    Hello, Can anyone point me in the direction of any good material for 33kV/11KV transformer protection schemes and how the various relays discriminate with each other. Thanks
  6. STONE85

    Data network extension to a field jb

    Thanks for the reply. It would just be to connect the remote buildings to the existing intranet. So if we had a switch in a main building and ran a fibre out to a JB then this could allow the remote building to connect to the intranet or would we need a field mounted panel inclusive of a switch...
  7. STONE85

    Data network extension to a field jb

    Hello, I have a question regarding the extension of a data network. If we have a building with a data network and we wish to extend this network to a field junction box that will then allow approx 5 temporary buildings to connect to the data network. Would we need a small outdoor panel with a...
  8. STONE85

    Extension of a data network

    Thank you for the replies. I understand now, we would take a fibre from the existing switch to the new location and install a new switch here. We would then connect our devices ( computers, voip phones etc) into this new switch. Thanks again
  9. STONE85

    Extension of a data network

    Hello, I have a question regarding extending an existing data network to a new building. If there is only one data point required in the new building would a switch still be installed ? Is there another way to take the existing network to a connection point in the new building ? Thanks
  10. STONE85

    Cable grouping (circuits/cables)

    That’s great.Thanks for the reply.
  11. STONE85

    Cable grouping (circuits/cables)

    Hello, With regards to Trimble software for bs7671 cable sizing. I understand that a three phase circuit (No neutral) is one circuit and this can be achieved by 3 single core cables. Say for a “box” we have 5 single cables in parallel per phase (15 cables total) in Trimble for grouping purposes...
  12. STONE85

    IT earthing system

    Hello, I have a question with regards to Trimble cable calculations. Can Trimble be used for calculations with an IT earthing system? Thank you
  13. STONE85

    11kv Ring main

    Hello, I have a question in regards to 11kv ring main circuits. What is a closed ring? Am I correct with the following Say we have a switch board with two incoming supplies and a buscoupler splitting this board into two sections. Would this buscoupler be closed for a closed ring ? Thanks
  14. STONE85

    Feeder pillars

    Thanks for this. Another term they sometimes go by is power pillar or a power box. Thanks
  15. STONE85

    Feeder pillars

    Hello, I have a question regarding feeder pillars. When are these units best used, is it solely based on length of cable run ( e.g to save long runs) or are there other factors to consider? Thanks
  16. STONE85

    extension of site data network.

    Thanks for this. I will dig into this further. Thanks again.
  17. STONE85

    extension of site data network.

    Hello, There is a project to put in a new building and we will have to tie into the existing data network. I know we will need to provide a new switch in the new building but my question is how to tie this into the existing site network? Would this be by fibre cabling to a spare port on the...
  18. STONE85

    Feeder cable sizing bs7671

    Thanks for this. Just to be clear. From my second post. If we have three 100kw machines then the supply to each one of these must be rated for 100kw. The feeder cable supplying the building housing the machines may take into consideration that these machines will not all be running at the same...
  19. STONE85

    Feeder cable sizing bs7671

    Hello, I have a further query related to this topic if that’s ok. Say we have have three machines each rated at 100kw at full load. From the information I have there is diversity and load Ultilisation applied. This lowers the three machines and the third machine load figure is extremely small. I...
  20. STONE85

    Feeder cable sizing bs7671

    Thanks for this. That’s exactly what I was thinking.