  1. magoo2

    light in Hazardous areas

    The attachment says the opposite. They change from HPS to LED lights. HPS is an arc-type of light. If the glass shatters, you have an open arc. I'm guessing that is why they want to go with LED lights, but that is just a guess.
  2. magoo2

    Determining Transformer kVA ratings

    kVA = kW/PF Once they give you the power factor, you can see what kVA you need.
  3. magoo2

    BESS maximum number of MV transformers per feeder

    200 A loadbreak elbows are available at 34.5 kV. The 600 A elbows are non loadbreak. We used Cooper/Eaton.
  4. magoo2

    Using series capacitors to start a big induction motor

    I see 230 kV on the left side of your drawing, but what is the voltage level supplied to the motor? 25 kV, 35 kV? Also, what is the rating of the substation transformer and its impedance? A series capacitor will reduce the reactance to the motor and thus reduce the starting voltage flicker.
  5. magoo2

    Surge Arrester Blowing

    What is the subtransmission voltage and what is the MCOV of the surge arresters? How many times has this happened before (arresters blowing)?
  6. magoo2

    15kV temporary flexible cable

    You should be able to do this with standard jacketed URD cable. I'd probably go with EPR insulation and stranded conductor for flexibility. You don't want to special-order something like this unless you have a very long length that you're dealing with.
  7. magoo2

    DC Current for Sizing the XLPE Cable

    I agree with Bill's result.
  8. magoo2

    United Flight from Denver to Hawaii blows engine on takeoff

    https://www.dailymail.co.uk/news/article-9282215/United-Airlines-flight-makes-emergency-landing-dropping-debris.html Flight was able to land in Denver. No injuries reported. It was a Boeing 777.
  9. magoo2

    Radial and ill-conditioned power flow solution?

    I believe Allen J. Wood covered this in his book "Power Generation, Operation and Control". I don't have a copy but I believe it was published around 1983. We adopted his technique for a secondary network which had a high R/X ratio and conventional load flow techniques didn't work too well.
  10. magoo2

    GE Distribution Data Book - GET-1008L

    The last edition of the GE distribution data book was GET 1008M, published in 1980. I'll have to look for my pdf version but don't hold your breath.
  11. magoo2

    Determining Capacitance of a Three Phase Capacitor Bank

    Normally you want to work with ohms per phase and then get the capacitance. Given the 3-phase Mvar and line-to-line kV of the bank, not the nominal p-p voltage ohms = kV^2/Mvar You can also take the per phase Mvar and the phase-to-neutral kV rating of the bank and get the same result...
  12. magoo2

    DC offset during fault in capacitive circuit

    One further comment. DC offset is mostly a function of closing angle, i.e., the point of wave on which the fault occurs. So, whether you have a capacitor bank on the circuit or not, you will get DC offset strictly based on closing angle.
  13. magoo2

    Short Circuit Current at Light Post Help

    R/1000 = 2 X/1000 = 0.054 I'll ignore X because R/X is almost 40(37) so X is not significant. Using just R R/1000 * 0.45 * 2 = 2 * 0.45 * 2 = 1.8 ohms Using just the #12, you get the available fault current of 120/1.8 or 66.7 A So it looks like your calculations are close enough to being...
  14. magoo2

    DC offset during fault in capacitive circuit

    A large capacitor bank produces a high frequency discharge into the fault. This will offset the fundamental frequency current but I'm not sure if is considered DC offset. It is really fundamental frequency plus natural frequency (of capacitor bank). I did find a reference that might be helpful...
  15. magoo2

    Short Circuit Current at Light Post Help

    Mbrooke, If you look at the fault current at the transformer on a phase to neutral basis, 120 V/23132 A = 0.00518 ohms like you calculated. I don't have a table of small conductor sizes and I can't follow your equations. My suggestion is to simplify the setup and just consider the 450 ft of #12...
  16. magoo2

    Single Phase AC MOTOR stuck

    To start, I would suggest your taking a picture of the nameplate and giving more details like HP, voltage, speed, etc.
  17. magoo2

    Oil filled Transformer Ambient Derating- ANSI C57.91

    cherryg222 - I just saw your post when I submitted my response to cuky2000. If you are comfortable with a rule of thumb approach, then go for it. I really don't like it.