  1. undervoltage

    Communication Protocols

    Below link refers to a very good book on the Subject... http://www.kelm.ftn.uns.ac.rs/literatura/pdms/PracticalIndustrialDataCommunications.pdf
  2. undervoltage

    Communication Protocols

    I am not that much familiar with communication protocols. Can anyone suggest me some good reference so that I can study it from the Substation Communincation stand point. Thanks in advance.
  3. undervoltage

    Recommendations of short circuit software

    For low budget SKM is better for you. Its very cheap as compared to ETAP.
  4. undervoltage

    Light Fixtures 240V fixtures on 208V circuit?

    No harm, the output lux level will be less then what it should be at rated voltage.
  5. undervoltage

    Multi Function Protection Relays for MCCB

    Do we traditionally install a Multifunction Protection Relay on a Low Voltage MCCB? Will it operate like a Power Circuit Breaker from a Protection Relay? Thanks
  6. undervoltage

    Cable Trench

    With hot water pipes your cables will be derated. Also they may damage the insulation over the time and you may have to replace the cable completely.
  7. undervoltage

    CTs for Compact Space

    I am working on a retrofit for 480 Cutler Hammer switchgear where the width of each section is 21". I have to install CTs and I need window type 3000/5A relaying CTs which can be placed side by side.Can anyone suggest me CTs with small dimensions and suitable window size (max. 3 inches) for such...
  8. undervoltage

    Metering CT saturation

    At how many times of rated current normally a metering CT saturates? I have a metering CT of 0.3B0.5, 600/5A class and want to use it with a protective relay which will pickup at 600A. Can I use this CT with the relay or I need a relaying class CT? Thanks
  9. undervoltage

    Alstom grid NPAG new edition

    Thanks prc The correct link is below http://www.alstom.com/grid/npagrequest/
  10. undervoltage

    Voltage level for MCC

    *Voltage drop at the bus. You may check this by running a motor starting study.
  11. undervoltage

    Voltage level for MCC

    Depends upon your voltage drop particularly at the instant of motor starting and the no. of motors required to start at one time.
  12. undervoltage

    Direct Buried DC cable ampacity calculation for solar farm

    Calculate the applicable derating factor as per NEC or IEC which ever is applicable and make sure that your cable can carry 168A after being derated. For the derating due to grouping, refer to the vendor's catalogue. The optimum arrangement will depend upon the number of cables per group. It...
  13. undervoltage

    one NGR only

    But I believe, by keeping one generator grounded at one time, you keep the other two in operation even if there is ground fault on the distribution side since all the generators are synchronised.
  14. undervoltage

    one NGR only

    Well, I would like dpc any other senior member to reply to this.
  15. undervoltage

    Maximum Installed Lighting

    tctctraining: Long time when I worked on the Lighting Design. I will have to see it :-)
  16. undervoltage

    one NGR only

    I think he mean to say that he has 3 generators running in parallel but only one NGR is there and at one time only one of the generator is connected to the NGR. The remaining two generators run ungrounded. I have seen the same situation in one of the Power Plant for a fertilizers industry in...
  17. undervoltage

    Maximum Installed Lighting

    Check Illumination Engineering Society (IES) handbook.
  18. undervoltage

    81L/H Settings for Utility Feeders

    Thanks all for your valueable response.
  19. undervoltage

    81L/H Settings for Utility Feeders

    I dont have any local generation, I have two 13.8kV feeders from the local utility. Do I need 81L/H protection for my system? Any reference?
  20. undervoltage

    81L/H Settings for Utility Feeders

    Do we normally provide 81L/H protection settings for utility feeders at 13.8kV? Thanks