  1. slavag

    Parallell CT for 7UT86

    yes, it is standard solution for years
  2. slavag

    YNd11 (earth fault at delta side)

    59N, residual overvoltage protection (broken delta, voltage displacement, etc.) But, it is common detection for whole system. You can use Varmetric, IosinF0 for feeder detection.
  3. slavag

    Earth mat design Using ETAP software for Industrial substation (High Short current Fault)

    Good explanation of erdep!!! Saiedsadat, take in account, 400V is solid ground. important point: EN 50522:2010 Earthing of power installations exceeding 1 kV a.c.
  4. slavag

    Earth mat design Using ETAP software for Industrial substation (High Short current Fault)

    Do not need make such calculation in the 400V level with TNS system. Earth current is back via PEN. You have calculated on the 20kV side only.
  5. slavag

    Bucholz trip

    Best way is connect to high speed trip relay, and contact of trip relay to BI of SEPAM...
  6. slavag

    Bucholz trip

    Add 20ms delay for input operation
  7. slavag

    Bucholz trip

    Seems as some mistake in wiring or protective terminal configuration. Second option is some dip of DC and unwanted peak up of SEPAM input.
  8. slavag

    Kingsine or Ponovo experience

    Sverker900, simple and good device
  9. slavag

    Minimum power loss in a transformer

    Please see attached document: https://assets.new.siemens.com/siemens/assets/api/uuid:fc71732f-96bc-4fae-96e2-1b5a78df7167/ecodesignleaflet.pdf
  10. slavag

    Multi Generators - One neutral grounded

    Directional earth fault protection is used. Toward to to the generator.
  11. slavag

    430 MVA GSU Tripping on 51G1N (Neutral Ground Overcurrent)

    Sorry, not understand. 51GN is direct connection,
  12. slavag

    Io Residual current in protection relay settings

    OK. next steps. 1. What is a setting ground fault and overcurrent of upstream breaker? 2. What is a data of 13.8/0.48kV transformer? ( setting of 20A, 1sec and 30A 0.5 sec....is not setting)
  13. slavag

    Io Residual current in protection relay settings

    Without short circuit study....not possible determinate setting. What is a setting for overcurrent?
  14. slavag

    Io Residual current in protection relay settings

    Hello that means, single phase short circuit current. In your case, system is solid grounded, its very high level of single phase short circuit current. Some one make short circuit study of system? Im not familiar with Vamp terminals. What is 0.67A ? Why 0.3PU is 30A? CT is 50/1 Phase CT is...
  15. slavag

    Io Residual current in protection relay settings

    What is a type of neutral grounding of the system? solid, low impedance, high impedance, compensated? What is a phase to neutral fault current?
  16. slavag

    ABB REM620 Thermal Overload Function Test Reset Problem

    It is some old information about MPTTR function, for REF615. Hope it is help https://www.dropbox.com/s/h6h9ksea4for386/MPTTR.rar?dl=0
  17. slavag

    Shielded Cable for CT & PT Wiring

    We are always ground shield of any control cable ( include CT, VT) on the both side.