  1. UFT12

    Fire Pump Sizing

    To add to this, NFPA 1 is also in alignment with the above. 18.4.4.4 * Required Fire Flow and Automatic Sprinkler System Demand. For a building with an approved fire sprinkler system, the fire flow demand and the fire sprinkler system demand shall not be required to be added together. The...
  2. UFT12

    Obstruction criteria FM DS 02-00

    Thanks Travis, appreciated. I knew there had to be a limit for that. Strange that FM so meticulous with their standards not giving this vital information.
  3. UFT12

    Obstruction criteria FM DS 02-00

    Hello. I would appreciate if someone could enlighten me about obstruction criteria for storage sprinklers per FM DS 02-00. Table 2.5.4.5.4.1 of Interim revision January 2024, tells that when the obstruction is less than 24", it needs to be checked where the obstruction is located to avoid extra...
  4. UFT12

    NFPA 14 - Looped Standpipes and Flow Splitting

    The 2024 edition has section 9.4 to address this. Section 9.4.3 seems to imply that multiple interconnections for wet systems are allowed and the rest of the requirements are not against it. In the 2019 edition, there was a limitation that required check valves be installed at the bottom of the...
  5. UFT12

    NFPA XX VS AS 2419 - Hydrant design

    Check chapter 18 of NFPA 1 .
  6. UFT12

    Sprinkler Obstruction and Radiant Heating Panels

    Have you contacted the designer or the manufacturer of the heating radiators for recommendations such as indicative heat dissipation patterns and prevailing temperatures? For example, right next to the panel the radiation is expected minimal while convection typically does not run horizontally...
  7. UFT12

    Sprinklers under ducts

    1m in not 4 ft. You probably mean 1.2 m. Assuming we abide to NFPA 13, the sprinkler deflector above the duct will most likely be even less than 25 cm which means that you need to apply the three-times rule for obstructions lying in the first 18 in (46 cm) vertically from deflector. This is...
  8. UFT12

    Greetings, I have a high rise ho

    The 20 psi refer to the hydrant while the 225 surely not on the connection rather to the pump. So these do not seem comparable. Anyway, although your though appears reasonable to me, you are pushing your pump to its limit (+50% from rating point, 1500 gpm). That may not be the best idea...
  9. UFT12

    U-Haul warehouse 48 height ceiling

    Sorry, I had other type of containers in mind. It makes sense. These can be like rooms without protection.
  10. UFT12

    NFPA 20: Type of valve at test connection on sensing lines

    I ve seen many installations with ball valves and no, they don't have to be listed since the function of the system is not depended on them in case of malfunction.
  11. UFT12

    U-Haul warehouse 48 height ceiling

    I'm not sure what exclusion are you talking about. Section 3.9.1 does not exist. Also I am not aware of any exclusion about household commodities imposed by NFPA 13. The standard does not exclude commodities based on the occupancy the items belong to rather combustibility, type of packaging and...
  12. UFT12

    Sprinkler fire protection system for cigarettes manufacturing and storage facility

    You can slide up the curve III in Fig. 21.2.2.1 but you can't reach 8.2 mm/min since the curves are trimmed. So I don't see how you can get away without utilizing K115 heads unless you have high temp. heads already which this would enable you to use Fig. 21.2.2.2 with K80 (sliding up to reach...
  13. UFT12

    Sprinkler fire protection system for cigarettes manufacturing and storage facility

    Have you checked 21.1.4? Also, for a flow of 150 lpm and a density of 14.5 mm/min, the area of coverage results to 150/14.5 = 10.34 m² which seems it does not satisfy 10.2.4.2.1(d).
  14. UFT12

    NFPA FIRE PROTECTION HANDBOOK 21ST EDITION.

    Hasan, have you checked this? www.nfpa.org/NFPA-LiNK
  15. UFT12

    NFPA FIRE PROTECTION HANDBOOK 21ST EDITION.

    Sure. Here it is https://catalog.nfpa.org/Fire-Protection-Handbook-21st-Edition-P22371.aspx?order_src=s420
  16. UFT12

    recommended minimum separation distances between crude oil tanks According to NFPA 30

    The GAPS guidelines are written from an insurance point of view which are concentrated mostly on property protection. NFPA standards are supposed to be part of a statutory body which impose the minimum requirements mostly for life safety. Therefore, it is expected that sometimes considerable...
  17. UFT12

    Distance between SPK

    Then the beam rule applies. See the requirements of 10.2.7.
  18. UFT12

    Distance between SPK

    The situation described in 9.3.5 is not for draft curtains between sprinklers, rather parallel. If this is your case, see figure A.9.3.5 for the maximum distance.