I would just add to dpc's commentary: close-coupled switchgear, i.e. perhaps a power style transformer that is a few feet away from a switchgear lineup, will likely have a SLG fault current (3*Io) greater than the 3PH fault current. As dpc addresses above, this is cause for concern.
Mike
Right or wrong...I used the following:
<5% VTHD
<33% ITHD
Anything above those #'s, I would look into filtering if operational/equipment issues were noticed, etc. I hadn't experienced any operational down-sides to those #'s, but your mileage may vary depending on your installation.
Mike
If I'm not mistaken, if a UPS fails, it will want to transfer from the inverter/rectifier to its static bypass. Maybe this is why the time delay on your UV release didn't work.
Mike
Is the UPS operating in "energy savings" mode rather than double conversion? I wonder if there is some issue w/ syncing as previously mentioned. If it is operating in D-C mode, then maybe an issue with the rectifier/inverter?
Mike
I'll answer my own question in this thread:
According to IEEE C62.92.2, separate neutral grounding reactors is considered an outdated method of gen grounding. So, we'll go with a grounding transformer w/ a resistor and deal with the existing equipment issues as needed.
Mike
Thanks for the comments thus far:
1) We have no direct 15kV loads. We have about 60, Delta-Wye grounded transformers which are part of the electrical service entrance(s). We have both 480/277V and 208/120V secondaries.
2) We didn't consider a Wye-Delta grounding transformer, but doesn't mean...
All,
I am the owner's rep for a project in design, which is to install two 2.1MW, 15kV class rotary UPSs (coupled with diesel engines for extended outages). Upon loss of utility, we obviously lose our ground reference.
Two options:
1) Zig-zag w/ resistor (LRG). We would have to upgrade our...
Double check your electrode configurations as I am doubtful of a 4000A breaker having VCB (more likely HCB), but could be wrong. Also SWGR instead of PNL?
Mike
If you are in the US..I believe the new building code requires some type of closed circuit camera to monitor the elevator in case of a passenger is stuck inside. Check the IBC.
Mike
I would say convention is to wire the disconnect such that when the switch is opened, the knife side of the switch is de-energized (switch base side is hot, knife side not). I'm not sure voltage separation/clearances can be maintained if the switch is opened as the knives will be energized so...
Landed on always using the new door approach. Less time for connects in the field, etc.
Mike
PS I haven't had a negative experience with either option.