  1. slavag

    Power Transformer 300/150/150MVA cooling type.

    Dear PRC Thanks a lor for your help!
  2. slavag

    Power Transformer 300/150/150MVA cooling type.

    In case of ONAN/ONAF we use 0.6..0.7/1 Sonan / Sonaf. What is recommendation for ONAN/ODAF?
  3. slavag

    78V/Vector Shift/Voltage Surge/Vector Surge protection in the Distribution Generation system

    Dear Colleagues. What is experience with this type of anti-islanding protection? What is regulation/standards in your system. Thanks in advance
  4. slavag

    Power Transformer 300/150/150MVA cooling type.

    Dear Colleagues. What is preferable cooling type of Power Transformer 300/150/150MVA 161/33/33kV? It will be Step-Up transformer. Generation type : PV and BESS. ONAN/ONAF ONAN/ONAF/OFAF ONAN/ONAF/ODAF Thanks a lot in advance!
  5. slavag

    Parallell CT for 7UT86

    yes, it is standard solution for years
  6. slavag

    YNd11 (earth fault at delta side)

    59N, residual overvoltage protection (broken delta, voltage displacement, etc.) But, it is common detection for whole system. You can use Varmetric, IosinF0 for feeder detection.
  7. slavag

    Earth mat design Using ETAP software for Industrial substation (High Short current Fault)

    Good explanation of erdep!!! Saiedsadat, take in account, 400V is solid ground. important point: EN 50522:2010 Earthing of power installations exceeding 1 kV a.c.
  8. slavag

    Earth mat design Using ETAP software for Industrial substation (High Short current Fault)

    Do not need make such calculation in the 400V level with TNS system. Earth current is back via PEN. You have calculated on the 20kV side only.
  9. slavag

    Bucholz trip

    Best way is connect to high speed trip relay, and contact of trip relay to BI of SEPAM...
  10. slavag

    Bucholz trip

    Add 20ms delay for input operation
  11. slavag

    Bucholz trip

    Seems as some mistake in wiring or protective terminal configuration. Second option is some dip of DC and unwanted peak up of SEPAM input.
  12. slavag

    Kingsine or Ponovo experience

    Sverker900, simple and good device
  13. slavag

    Minimum power loss in a transformer

    Please see attached document: https://assets.new.siemens.com/siemens/assets/api/uuid:fc71732f-96bc-4fae-96e2-1b5a78df7167/ecodesignleaflet.pdf
  14. slavag

    Multi Generators - One neutral grounded

    Directional earth fault protection is used. Toward to to the generator.
  15. slavag

    430 MVA GSU Tripping on 51G1N (Neutral Ground Overcurrent)

    Sorry, not understand. 51GN is direct connection,