Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

Search results for query: *

  1. JuanBC

    Arc resistant switchgear - fault duration 1s?

    Hello everyone, Thanks for your comments I reviewed many vendors available in the market and, as you indicated, 300ms in the standard value I used to think that more than 500ms was required to coordinate the incomer with the outgoing circuit-breakers but I think that is only required in MV...
  2. JuanBC

    Arc resistant switchgear - fault duration 1s?

    dpc, thanks. I like your comment on the following: The problem is how to calculate arc current before buying que equipment and performing protective devices coordination study 😅 JBC ....... "The more I read, the more I acquire, the more certain I am that I know nothing"
  3. JuanBC

    Arc resistant switchgear - fault duration 1s?

    Hi jraef, thanks for posting. So based on IEEE point of view, I shouldn't set the incomer overcurrent protection to more than 500ms, right? That seems quite low if you need it to coordinate with 3 or more downstream protective devices I know short circuit withstand ratings and arc flash...
  4. JuanBC

    Arc resistant switchgear - fault duration 1s?

    Hello guys, I would like your opinion regarding the following issue: Since the short-circuit level in an installation I am designing is about 60kA, I am asking for IEC LV switchgears rated 65kA/1s and also being arc resistant (65kA/1s arc duration) One of the bidders is offering 65kA/1s...
  5. JuanBC

    Help! 4000V IP24W IC01 motor located outdoors

    Hi jraef, Thanks for your replay. I think the same as you but I wanted to have another point of view MV motors to be installed range from 800 to 2500 kW Regards, JBC ....... "The more I read, the more I acquire, the more certain I am that I know nothing"
  6. JuanBC

    Help! 4000V IP24W IC01 motor located outdoors

    Hello, quick question: Is a 4000V IP24W IC01 motor suitable to be located outdoors in a really rainy power plant? What about IP24W IC 411? Does this combination even exist? Many thanks, JBC
  7. JuanBC

    DC & UPS System Design

    Hello, I am working on a project for a Power Plant that requires a DC+UPS system like the one in the picture below The two redundant battery chargers as well as the two inverters are a 'customer requirement', but it remains 'open to interpretation' if two STS (Static-Transfer-Switches) + two...
  8. JuanBC

    Positive , Negative and Zero

    Hi marvinc24, If you run a short-circuit calculation (at least under IEC), Pos-Neg & Zero sequence impedances are shown in the 'output report' for each bus faulted Regards, JBC ....... "The more I read, the more I acquire, the more certain I am that I know nothing"
  9. JuanBC

    4.16kV Switchgear Technical Specification

    Hello, I need to specify a 4.16 kV Switchgear for a Thermal Generation Plant. I have some 'examples' but I would like another one. I need to write an engineering deliverable. Does anyone have a Technical Specification (word/pdf) to share? I want to cover every important 'topic' Thank you in...
  10. JuanBC

    Ground wire (PE conductor) within power cable?

    Thank you all for your reply I am reading that cable trays and metallic conduits (as RMC or IMT) can be used as EGC as long as they meet some requirements. In that case, an "extra" EGC within the power cable is not necessary, am I right? Is this still valid if the entry to the boards/motors...
  11. JuanBC

    Ground wire (PE conductor) within power cable?

    Hi, Imagine a big (O&G/power plant) facility (composed of many buildings and equipment) that has a large grounding mesh beneath it. This mesh is completely interconnected with each other. Is it mandatory that every power cable feeding different boards/motors in this installation has a...
  12. JuanBC

    460VAC 60Hz Motor on 400VAC 60Hz?

    Hello, Motor rated power and torque (output) is directly proportional to the square of the voltage. If you use a 460Vac motor on a 400Vac network, it won't be able to develop the "rated torque", and instead, will develop (400/460)^2 = 75.6% of it. What will happen depends on the mechanical...
  13. JuanBC

    ETAP Libraries (.lib)

    Hi PoliPoli, Find attached the ones I've got. I asked them to ETAP HelpDesk as I need them. You can do the same here https://helpdesk.etap.com/cgi-bin/wonderdesk.cgi (you need an original serial no.) Regards, Juan JBC ....... "The more I read, the more I acquire, the more certain I am that I...
  14. JuanBC

    Teaching myself autocad vs formal class

    Hi, Option C for those who are poor: Watch youtube videos and look for free online courses. There are lot of them JBC ....... "The more I read, the more I acquire, the more certain I am that I know nothing"
  15. JuanBC

    Transformer Impedance definition

    Also take a look at this: https://www.eng-tips.com/viewthread.cfm?qid=440427 JBC ....... "The more I read, the more I acquire, the more certain I am that I know nothing"
  16. JuanBC

    Transformer Impedance definition

    Hi. Take a look at the picture attached. It is from IEC 60076-5. GL JBC ....... "The more I read, the more I acquire, the more certain I am that I know nothing"https://files.engineering.com/getfile.aspx?folder=a39cb229-e1b9-4d82-99f1-0b8ff13e97e3&file=IEC60076-5.png
  17. JuanBC

    [IEC Cable-sizing worksheet] Sharing own creation

    Thank you! I hope you find it useful. If you have any questions, let me know JBC ....... "The more I read, the more I acquire, the more certain I am that I know nothing"
  18. JuanBC

    [IEC Cable-sizing worksheet] Sharing own creation

    Hi 7anoter4, Try with this file (.xltm). Tables are in hidden sheets. The macros are only used to open different menus but they do not take part in the calculation, all the calculation is perform "comparing" tables. Regads, JBC ....... "The more I read, the more I acquire, the more certain I...
  19. JuanBC

    [IEC Cable-sizing worksheet] Sharing own creation

    Hello guys, I would like to share with you a worksheet that I've developed, aimed to size LV power cables (Up to 1kV) using IEC 60364-5-52 (https://webstore.iec.ch/publication/1878) Some information may be weird to many of you, since I live in Argentina and here we do not follow just one...
  20. JuanBC

    Notation for multi-core cables having PE (Protective Earth/Ground conductor) in the same jacket

    Hi Bill, What is the origin of that designation? Are manufacturers trade-names or are they specified in a standard? Here in Argentina, we don't use that names. I just want a generic notation for multi-cores cables included a PE conductor Thanks, JBC ....... "The more I read, the more I...
Back
Top